Time | Kumbotso TRX Load | Dangora TRX Load | Funtua TRX Load | Gazoua | Azare | TOTAL KEDCO LOAD |
---|---|---|---|---|---|---|
13:00 | 312 | 16.1 | 17.1 | 30.5 | 1.5 | 313.2 |
14:00 | 302 | 15.4 | 17.1 | 31 | 2.9 | 300.6 |
15:00 | 271 | 5.1 | 0 | 31.5 | 2.6 | 242 |
Station | Turbine | Peak Gen (MW) | Off Peak Gen (MW) |
---|---|---|---|
KAINJI | HYDRO | 197 | 198 |
JEBBA | HYDRO | 470 | 471 |
SHIRORO | HYDRO | 450 | 450 |
EGBIN ST2 - 5 | STEAM | 210 | 201 |
SAPELE | STEAM | 66 | 67 |
DELTA | GAS | 400 | 400 |
AFAM IV-V | GAS | 0 | 0 |
GEREGU GAS | GAS | 282 | 145 |
OMOTOSHO GAS | GAS | 187.9 | 177.3 |
OLORUNSOGO GAS | GAS | 170.9 | 156 |
# | Last Name | Username |
---|---|---|
1 | KANO | 174.6 |
2 | JIGAWA | 11.4 |
3 | KATSINA | 35 |
PLEASE NOTE THAT FUNTUA RECORDED 15.1MW AT 1000HRS AS PART OF KATSINA LOAD WHILE DUTSE & HADEJIA RESPECTIVELY RECORDED 12.9MW & 5.2MW.
Feeder Name | Tripping Date & Time | Relay Indication | Restoration Date & Time | Downtime | Present Status | Brief Description |
---|---|---|---|---|---|---|
33KV DAWANAU | 21/10/2016 05:24:00 | O/C R PHASE | 21/10/2016 14:00:00 | 0 Days 8 Hrs 36 Min | STILL OUT | 0.6MW WAS INTERRUPTED. AFFECTED REGION INFORMED. |
33KV MALUMFASHI | 21/10/2016 02:06:00 | EARTH FAULT | 21/10/2016 14:00:00 | 0 Days 11 Hrs 54 Min | STILL OUT | 13MW WAS INTERRUPTED. AFFECTED REGION INFORMED. |
33KV DANDUME | 21/10/2016 02:40:00 | EARTH FAULT | 21/10/2016 14:00:00 | 0 Days 11 Hrs 20 Min | STILL OUT | 4MW WAS INTERRUPTED. AFFECTED REGION INFORMED. |
33KV LAW SCHOOL | 21/10/2016 09:34:00 | EARTH FAULT | 21/10/2016 14:00:00 | 0 Days 4 Hrs 26 Min | STILL OUT | 9.2MW WAS INTERRUPTED. AFFECTED REGION INFORMED |
33KV KAFIN HAUSA | 21/10/2016 09:20:00 | EARTH FAULT | 21/10/2016 14:00:00 | 0 Days 4 Hrs 40 Min | STILL OUT | 2.4MW WAS INTERRUPTED. AFFECTED REGION INFORMED |
33KV KURNA | 21/10/2016 11:43:00 | O/C B & E/F | 21/10/2016 14:00:00 | 0 Days 2 Hrs 17 Min | STILL OUT | 7.5MW WAS INTERRUPTED. AFFECTED REGION INFORMED |
33KV CLUB | 21/10/2016 09:57:00 | O/C B & E/F | 21/10/2016 11:46:00 | 0 Days 1 Hrs 49 Min | RESTORED | 2.4MW WAS INTERRUPTED. AFFECTED REGION INFORMED. NOTHING DISCOVERED UPON PATROL |
33KV GEZAWA | 21/10/2016 12:05:00 | EARTH FAULT | 21/10/2016 14:00:00 | 0 Days 1 Hrs 55 Min | STILL OUT | INSTANT TRIPPING UPON TRIAL RECLOSURE |
33KV NNPC | 21/10/2016 12:53:00 | O/C ALL PHASES | 21/10/2016 14:00:00 | 0 Days 1 Hrs 07 Min | STILL OUT | 7.5MW WAS INTERRUPTED. AFFECTED REGION INFORMED |
11KV MAKAMA | 20/10/2016 20:10:00 | NO INDICATION | 21/10/2016 14:00:00 | 0 Days 17 Hrs 50 Min | STILL OUT | 0.4MW WAS INTERRUPTED. AFFECTED REGION INFORMED. |
11KV KABUGA | 21/10/2016 09:18:00 | EARTH FAULT | 21/10/2016 14:00:00 | 0 Days 4 Hrs 42 Min | STILL OUT | 5.3MW WAS INTERRUPTED. AFFECTED REGION INFORMED. |
11KV TOKARAWA | 21/10/2016 10:00:00 | O/C YB & E/F | 21/10/2016 14:00:00 | 0 Days 4 Hrs 00 Min | STILL OUT | 0.5MW WAS INTERRUPTED. AFFECTED REGION INFORMED. |
Feeder Name | Feeder Status | Remarks |
---|---|---|
33KV DANDUME | SEGMENTED | FEEDER WAS SEGMENTED ISOLATING MASKA |
33KV MALUMFASHI | SEGMENTED | FEEDER WAS SEGMENTED AT DANJA AND MAKURDI T-OFFS DUE TO A FAULT |
33KV KAZAURE | SEGMENTED | FEEDER IS NOT AVAILABLE ON FULL LENGTH DUE TO FAULT AFFECTING INGAWA & GWIWA AXIS. |
33KV DAWANAU | SEGMENTED | FEEDER WAS SEGMENTED AT FILLIN KWALO AND KOFAR RUWA |
33KV KWANKWASO | SEGMENTED | FEEDER WAS SEGMENTED AT GARO |
33KV GEZAWA | SEGMENTED | FEEDER WAS SEGMENTED AT BARWA VILLAGE |
33KV KAFIN HAUSA | SEGMENTED | FEEDER WAS SEGMENTED AT BULANGU & MARKE |
33KV FALGORE | SEGMENTED | FEEDER WAS SEGMENTED AT YAR YASA |
33KV KARAYE | SEGMENTED | FEEDER WAS SEGMENTED AT KARAYE |
33KV GUMEL | SEGMENTED | FEEDER WAS SEGMENTED ISOLATING GUMEL |
33KV POLY | SEGMENTED | FEEDER WAS SEGMENTED WITH BATSARI, RIMI AND MANI AXIS SEGMENTED |
33KV LAW SCHOOL | SEGMENTED | FEEDER WAS SEGMENTED WITH BEBEJI AXIS SEGMENTED |
33KV DAURA | SEGMENTED | FEEDER WAS SEGMENTED AT KAYAWA VILLAGE DUE TO CUT CONDUCTOR @ MAZOJI VILLAGE |
11KV MAIRUWA | SEGMENTED | FEEDER WAS SEGMENTED WITH KUMI VILLAGE ISOLATED |
POWER DISTRIBUTION

Kano Electricity Distribution Company is responsible for distributing electricity between three states which are Kano, Katsina and Jigawa.
Overview of kedco distribution network coverage :
Kano Electricity Distribution Company gets its bulk power supply from the following Transmission Stations;
1. Kumbotso Transmission Station 4x150MVA, 330/132KV Transformer. Ex-Kaduna Regional Transmission Station.
2. Zaria Town Transmission Station 1x60MVA, 132/33KV Transformer feeding Funtua Town in Katsina State.
3. Jos Transmission Station 30MVA, 132/33KV Transformer feeding Tudun Wada and Doguwa Local Government
Areas of Kano State via Saminaka 33KV feeder.
The bulk power supply from the Transmission Station is wheeled to a number of Sub-Transmission Stations located at different areas within the geographical area of Kano, Katsina and Jigawa States.
The Sub transmission station wheels power to various Distribution Injection Substations.